Input Voltage for Frequency 110/230/415 Volts, 50/60/40Hz (or any other), |
|
| |
Converters : |
|
single or three phase A.C. as per requirement or specifications. |
|
| |
Input Voltage Tolerance : |
|
±10% of nominal input voltage. (wider tolerance if possible on request.) |
|
| |
Output Power(at unity P.F) : |
|
100,250,500 & 750VA and 1, 1.5, 2, 3, 4 & 5 KVA In single phase output. 100, 250,500 & 750VA1, 1.5, 2, 3, 4,5,7,5, 10 in three phase output. |
|
| |
Output Voltage : |
|
115 Volts single phase or line to neutral in case of three phase (standard). Any other voltage on request. (Typical 36V, 220V single or three phase) |
|
| |
Output voltage settability : |
|
±5V standard, ±10V optional at extra cost. |
|
| |
Output Regulation a) Line : |
|
better than ±2%, against input voltage variation of ±10% of nominal input. |
|
| |
b) Load : |
|
better than ±2%, against load current variation from no load to full load. |
|
| |
Output Amplitude Stability : |
|
better than ±2%, against time (8 hrs.) and temperature (50°C change) |
|
| |
Load power factor : |
|
0.8 lagging to unity (Derate power capacity proportionately for load of other than unity power factor Derating to 70% at 0.8PF) |
|
| |
Output Frequency : |
|
any frequency from 40Hz to 1,000 Hz (fixed or variable). |
|
| |
Output Frequency stability : |
|
better than ±1% against input voltage or load current variation. (better than ±0.05% for crystal controlled models at option for selected frequencies at extra cost). |
|
| |
Wave from Distortion : |
|
less than 3% for load variation from no load to full load (resistive) and permissible line voltage variation. |
|
| |
RF Interference (Conducted & Radiated) : |
|
NIL |
|
| |
Peak Efficiency (Inversion) : |
|
better than 60% at full load and minimum input voltage. |
|
| |
Overall Conversion Efficiency : |
|
Around 50% |
|
| |
Protection for Output : |
|
Fast acting solid state protection for overload and continuous short-circuit to protect internal circuitry and delayed electromagnetic trip, over and above solid state protection to protect load against over temperature, UV, OV (optional) By mcb/fuse for Frequency Converter. |
|
| |
For Input : |
|
against under voltage & over Voltage (optional)
Input present, Output present, OL Trip (standard)
|
|
| |
Metering : |
|
Analogue for digital meters for monitoring input voltage, output voltage and load current & digital frequency meter for output frequency can be provided at extra cost. |
|
| |
Annunciation : |
|
Can be provided on request at extra cost & if feasible. |
|
| |
Environment : |
|
-0°C to 55°C, upto 95% RH non-condensing. |
|